Cross-Bonding Link Box
High Voltage Solutions

Cross-Bonding Link Box

Designed for cable sheath protection in cross-bonding systems. It effectively reduces induced sheath currents and minimizes power losses, ensuring reliable operation for 10kV to 110kV electrical networks.

  • Material: Premium 304 Stainless Steel
  • Voltage Range: 10kV, 35kV, 66kV, 110kV
  • Protection Level: IP55, IP56, IP66, IP68
  • Standards: GB11032-2000, IEC6009-4, DL/T401-2002

Overview & Environmental Conditions

Scope of Use: Suitable for cable sheath protection grounding boxes, direct grounding boxes, cross-bonding boxes, and sheath insulation monitoring boxes. These units are designed as three-phase common bodies (please specify if single-phase is required).

  • System Rated Voltage: Up to 110kV (10kV standard baseline)
  • Cable Nominal Cross-section: 25 - 800mm²
  • Rated Frequency: 50Hz / 60Hz
  • Temperature Range: -22°C to 40°C
  • Altitude: Below 3000m (Please specify if operation is above 3000m)
  • Installation Methods: Wall-mounted, buried, bracket-mounted, floor-standing, concealed (embedded).

Factory Testing & Performance

DC Withstand Voltage

5.5kV, 1 min (No flashover/breakdown)

Short-time Withstand Current

20 kA (Main Circuit)

Peak Withstand Current

50 kA (Main Circuit)

Lightning Impulse

185 kV

* Mechanical stress test verified: No cracks on the shell, no damage affecting electrical performance.

Installation Process

  1. Strip the insulation layer of the cable to make the exposed conductors the same length as the length of the terminal hole.
  2. Clean the objects inside the box.
  3. Remove the terminal blocks inside the box, press the cut grounding cable and the terminal block together, insert the terminal block into the inlet of the box, and fix it with screws.
  4. After fixing the first cable, insert the second cable, repeat the operation until all grounding cables are fixed.
  5. Fill rubber strips between the outlet pipe and the grounding place, fix the cable in the middle of the outlet pipe.
  6. Seal the outlet pipe with waterproof tape.
  7. Apply Heat-shrink tubing on the outlet pipe.
  8. Seal the two ends of the heat-shrink tubing with rubber insulation tape.
  9. Cover PVC tape on the waterproof tape, half-cover with two layers.
  10. Clean the objects inside the box again to ensure no debris remains.
  11. Install the sealing gasket and the box cover. Important: Do not tighten screws all at once. Tighten in three rounds to prevent box cover deformation.

Selection Models

Standard thickness: 1.5mm. All include Heat shrinkable tape and waterproof composite tape.

Model / Specs Dimensions (mm)
10kV (4 holes)
40*40mm Cu
440*370*180
35kV (4 holes)
40*40mm Cu
440*370*180
66kV (4 holes)
40*40mm Cu
500*410*210
110kV (4 holes)
40*40mm Cu
500*410*210
10kV (7 holes)
40*40mm Cu
550*400*200
35kV (7 holes)
40*40mm Cu
550*400*200